A CCTV contractor installs sixteen 12V adapters in a rack, feeds them from one circuit, and the breaker trips every time the cabinet is powered up. Nothing is faulty. Each adapter draws under an amp in normal operation, the sum is far below the breaker rating, and every unit carries a valid certificate. The problem is invisible on a datasheet because it lasts less than ten milliseconds: at the instant of switch-on, each adapter’s input capacitor charges from empty and behaves briefly like a short circuit.
That brief short is inrush current, and it is the specification most likely to be missing from a bulk purchase order and most likely to cause a site complaint after installation. This article covers what causes it, how the standards treat it, what the numbers usually look like for external adapters, and the practical checks that prevent a cabinet full of adapters from tripping a breaker.
Why an adapter draws a spike before it draws anything useful
An AC-DC adapter rectifies mains and stores energy in a bulk capacitor on the primary side. At the moment mains is applied, that capacitor is at zero volts. The rectifier sees a very low impedance load — effectively the capacitor plus the wiring and the effective series resistance — and current rises until the capacitor charges. With a typical bridge rectifier and a few tens of microfarads, that charging interval is a few milliseconds, and the peak can reach tens of amps on a 24W unit.
Two conditions make it worse:
- Closing at peak mains voltage. Switch-on is random with respect to the AC waveform. Worst case is right at the crest of the sine wave, and that worst case is what a specification should cover, not the average.
- Closing with the capacitor fully discharged. Adapters that were switched off and left to bleed down have empty capacitors; a quick off-on cycle can find the capacitor partly charged and produce a lower peak, which is why an intermittent fault is so hard to reproduce during a site visit.
The mitigating part is usually an NTC thermistor in series with the input. Its resistance is high when cold and falls as it self-heats, so it limits the initial spike and then stops wasting power in normal operation. That behaviour explains a second characteristic worth knowing: if the adapter is switched off and on again quickly, the thermistor is still hot and its resistance still low, so the second inrush can be higher than the first. It also explains why a unit that passed a cold-start test can still trip a breaker in a fast power-cycle scenario.
Two standards that bear on inrush, for different reasons
IEC 61000-3-3 — voltage fluctuations and flicker
This is the EMC standard that limits how much a load may disturb the supply voltage as seen by other equipment on the same network. It is expressed in terms of relative voltage change and flicker severity, and it is the document a buyer should look for when a product will be installed in numbers on one distribution board. An installation of many identical adapters behaves differently from one adapter measured alone: the disturbances add, and the standard’s method is designed around that reality rather than around a single unit on a bench.
In practice, most small external adapters are assessed under light-connection limits rather than against individual flicker measurement. Do not read a certificate as proof that sixteen of them on one circuit are fine — the certificate speaks to one unit’s behaviour in a test setup, and the installation is a system-level question.
IEC/EN 62368-1 — the safety side
Safety standards care about inrush primarily through component stress: the input fuse, the rectifier, the thermistor and the PCB traces must survive repeated worst-case switching without degradation. This is why an adapter can appear to pass everything and still fail after a season of hard power cycling in a location where the mains is switched at the wall every day — the components were sized for a specification that did not mention cycling.
Typical magnitudes, so you can sanity-check a claim
Numbers vary with topology and input voltage, but the ranges below are useful for spotting a quotation that is clearly optimistic. Values are peak cold-start current at 230V, single unit.
| Rated output | Typical cold-start inrush peak | Half-cycle energy behaviour |
|---|---|---|
| 12W–24W | 15A–30A | Short spike, few milliseconds |
| 36W–60W | 25A–45A | Larger bulk capacitor, longer charge |
| 90W–120W | 40A–70A | Needs deliberate limiting; thermistor alone often insufficient |
| 150W+ (desktop type) | 60A–100A+ | Active inrush limiting is normally the only way to stay inside installation limits |
Ask for the measured waveform, not just a number. What matters for a breaker is the current-time integral, not the peak alone: a 60A spike lasting two milliseconds is a different problem from a 30A spike lasting twelve milliseconds, even though the first number looks worse. An oscilloscope capture of input current at switch-on, with the time base stated, tells you which one you are buying.
Why breakers trip: the curve, not the rating
A 10A miniature circuit breaker does not trip at 10A. It trips on a time-current curve: a modest overload is tolerated for many minutes, while a large multiple of its rating trips within a fraction of a second through the magnetic element. Breakers are classified by that magnetic threshold:
- Type B — magnetic trip around 3–5× rated current. Common in domestic and light commercial boards.
- Type C — around 5–10×. Better tolerance for motor and capacitive loads.
- Type D — around 10–20×. Used where high inrush is expected.
Now the arithmetic that explains the CCTV cabinet. Sixteen adapters, each with a 30A cold-start spike, sum to a momentary 480A. On a 10A type B breaker, the magnetic threshold sits somewhere between 30A and 50A. Even accounting for the fact that the spikes are not perfectly simultaneous and that wiring impedance spreads them, the aggregate easily crosses the magnetic band — and the breaker opens. Nothing is defective, and no individual adapter is out of specification. The installation simply exceeded what the curve allows.
This is the point where the spec sheet matters most and where it is most often silent: the buyer needs the inrush figure to do a system calculation, and the supplier needs to know the intended installation to say whether one model or another is appropriate.
Practical fixes, in order of preference
- Staggered switch-on. Distribute adapters across two or three circuits, or use a sequenced power distribution unit, so the spikes do not superimpose. Cheapest and most effective, and it needs no change to the product.
- Higher breaker curve. Moving from type B to type C on the same rating buys tolerance for capacitive loads. This is an electrician’s decision and depends on the installation’s fault-loop characteristics — it is not a substitute for a correct design.
- Specify a model with active inrush limiting. Designs that use a relay or triac with a series resistor, instead of relying on an NTC alone, hold the peak to a defined level regardless of ambient and cycling history. Expect it in the higher power ranges and in units intended for rack installation.
- Choose one larger supply feeding several loads. A single 120W unit with a distribution harness has one inrush event instead of sixteen — often the cleanest answer for a rack, provided the DC wiring is sized for the total current and the loads tolerate a common rail.
- Avoid the quick off-on cycle in commissioning. Not a design fix, but worth writing into installation notes: repeated fast cycling finds the thermistor still hot and produces the highest peaks.
What to put in the purchase order
- Maximum cold-start inrush current at 230V and at 115V, single unit, with the measurement method stated.
- Whether switching is limited by an NTC thermistor, a fixed resistor with bypass, or active circuitry — and the behaviour after a fast power cycle.
- Input fuse rating and its time-current type, since this is what the inrush has to survive repeatedly.
- IEC 61000-3-3 compliance stated on the certificate, not assumed from the emissions report.
- Intended installation density: tell the supplier how many units sit on one circuit, and ask for a recommendation rather than a datasheet.
Two related notes. The load-side consequences of running many units from one rail — voltage drop across the distribution wiring — are covered in the output voltage reference, and the ageing effects of thermal and electrical stress are treated in the lifespan guide. Neither replaces asking for an inrush waveform.
Sorting a cabinet-sized installation before it ships
Describe the installation rather than just the unit: how many adapters, on how many circuits, which breaker type, and whether the cabinet is powered up as a whole or unit by unit. Send the total load per circuit along with the output voltage and current each device needs. The answer that comes back should be a model recommendation plus the inrush figure the electrician can put into a breaker calculation — from the 48W detachable adapter range for distributed cabinets, or a single 120W desktop supply with a distribution harness where one inrush event is preferable to sixteen.
If a quotation offers “low inrush” as a phrase without a peak value, a waveform, or the limiting method, it has not answered the question the installation is going to ask.